Counter-flow plate exchanger (recuperative)
Zero cross-contamination · 1% internal leakage
EC plug fans · single-phase 20A
NaviPad + Modbus + BACnet + TCP/IP

Systemair Topvex SC35-R-B

Counter-flow plate AHU · Hygiene-critical commercial scopes · 3,150 m³/h · £15,000 ex VAT equipment · Sizing adjustable to project

87.9%
heat recovery (EN 308 wet)
3,150m³/h
supply + extract
0%
cross-contamination
230V 1ph
single-phase mains
408kg
unit weight
2yr
warranty
get a quote
Whats App instead
Why switch

87.9% heat recovery (EN 308 wet)

Counter-flow plate · industry-leading efficiency

Zero cross-contamination

Plate physically separates streams · 1% internal leakage

Single-phase 230V · 20A

No 3-phase distribution required · 1.64 kW total

F7 supply + M5 extract filtration

EPM1 60% / EPM10 60% · pressure-monitored

Side-connected commercial AHU

867 mm wide · 408 kg · floor or low-clearance plant room

Lower power consumption

1.64 kW total · meaningfully lower than rotary equivalents

BMS-grade controls as standard

Navipad · Modbus RTU/RS-485 · BACnet/IP · TCP/IP

Hygiene-critical certified

Schools, daycare, dental, clinics · EcoDesign 2018 compliant

How it works
Specification
Control/App
Installation
components
Aftercare

Hygiene-critical commercial flow

A single Topvex SC35-R-B serves a hygiene-conscious commercial space — school, daycare, dental clinic, GP surgery, fitness studio, office. Filtered fresh air is supplied to occupied zones via a duct distribution system; stale air is extracted from kitchens, toilets, treatment rooms. EC plug fans run continuously to maintain balanced pressure. 3,150 m³/h on this configuration — adjustable to project at quote.

Counter-flow plate exchanger

The defining architectural choice. Supply and extract air streams pass each other in opposite directions across solid plates, transferring heat across the plate material without ever mixing. Result: zero cross-contamination, 87.9% heat recovery efficiency (EN 308 wet), 1% internal leakage measured. Recuperative heat exchanger — different from rotary regenerative units.

F7 + M5 filters integrated

SC35-R-B SKU includes F7 supply (ISO ePM1 60%) and M5 extract (ISO ePM10 60%) filters as standard — bundled into the unit price, not separate accessories. Eurovent certified. Filter monitoring via pressure transmitters with airflow-adjusted setpoint — controller alerts when pressure drop indicates change is due. DELTRI+ virucidal upgrade or HEPA H13/H14 available for hygiene-critical scopes.

Condensate handling

Counter-flow plate exchangers produce condensate when warm humid extract air meets the cooler plate surface — water needs to drain. The SC35-R-B has an integrated condensate drain pan with R½ connection. Plant location must accommodate drain routing to existing waste pipework. This is the architectural trade-off vs rotary AHUs (which transfer moisture and need no drain).

EC plug fans · low power

Two electronically commutated (EC) plug fans, 15–20% lower energy consumption than equivalent AC asynchronous motors. CAV (Constant Air Volume) cascaded extract control standard; VAV optional. Total power consumption 1.64 kW — meaningfully lower than rotary AHUs at the same airflow. Real heating-cost saving over building life.

Reheater & cooling options

Optional add-ons at order: EL (electric reheater), HW (hot water coil — for buildings with heat pump or boiler hot water available). Cooling coils: water (CWK / PGK series) or DX (DXRE series) for active summer cooling. SC35-R-B base configuration has no integrated reheater — added separately. Specified at design stage based on building's heating/cooling strategy.

Airflow 3,150 m³/h 3,150 m³/h supply + 3,150 m³/h extract at 115 Pa external pressure. Face velocity 1.7 m/s. CAV (Constant Air Volume) cascaded extract control.
Heat Recovery 87.9% 87.9% temperature efficiency wet (EN 308). 81.3% dry. 83.0% Ecodesign temperature ratio. Counter-flow plate exchanger (recuperative). Stepless capacity via modulating bypass control.
Sound Level 59 dB Sound power Lwa 59 dB. Sound pressure 45 dB(A) at 3 m. Tested per EN 13053. Acoustic silencers required for occupied office, school, retail, healthcare and fitness scopes.
Filters F7 / M5 F7 supply (ISO ePM1 60%) + M5 extract (ISO ePM10 60%) — integrated into SKU code (S-SC35-R-N-ePM1/60-CE-B-C1-ePM10/60-AC). Pressure-monitored — controller alerts when change is due. Removable from inspection access.
Power Supply 230V 1ph 1×230V + N + PE, 50/60 Hz, 20 A fuse. 1.64 kW total power consumption — single-phase. SFP int 1.04 kW/(m³/s). Direct drive EC fans, supply fan efficiency 66.0%, extract fan efficiency 62.8%.
Casing C5 / EN 1886 50 mm panels, double-skinned construction. EN 1886:2007 classifications: L2 (air leakage), D2 (mechanical), T2 (thermal), TB2 (thermal bridging). C5 corrosion class (EN ISO 12944-2). Width 867 mm.
Weight & Size 408 kg 408 kg unit weight. Duct connection 500 × 400 mm (4 connections — outdoor, supply, extract, exhaust). R½ condensate drain connection. Width 867 mm. Side-connected design — best suited to floor-mounted plant room installation.
Control NaviPad Access control system with NaviPad 7" IPS touchscreen (IP54). CU27-C2 WiFi unit with 27 physical I/Os. Modbus RS485, Modbus TCP/IP, BACnet/IP. Access Connect mobile app (iOS/Android). Systemair Connect cloud service available.
Ecodesign Approved Fulfils Ecodesign 2018. NRVU/BVU. Temperature ratio 83.0% nominal. SFP int 1.04 kW/(m³/s). Internal leakage 1%. External leakage 2%. Eurovent certified. ErP compliant.

Control

Topvex SC35-R-B ships with the Access control system — NaviPad touchscreen plus full BMS-grade communications. Designed for facility management at scale, with TCP/IP, Modbus, and BACnet integration as standard. CU27-C2 WiFi control unit with 27 physical I/Os.

NaviPad touchscreen

HTML5-based intuitive UI on a flat colour touchscreen, connected via 3 m flat cable. Mounts on the unit or on the wall — easy to detach for handheld use during commissioning. Real-time operating data, settable per project, custom labels for unit/alarms/components.

Modbus RTU + RS-485

Standard on every unit. Serial bus integration with BMS systems via Modbus protocol — typical for office, school and retail fit-outs where ventilation needs to coordinate with heating, lighting, and access control.

BACnet/IP + TCP/IP

BACnet over IP standard — the protocol most commercial BMS systems prefer. Plus direct TCP/IP web server access for browser-based monitoring without additional software. Multi-device monitoring across a local network of Topvex AHUs from one dashboard.

CAV / VAV airflow control

Constant Air Volume standard — fans hold a fixed airflow regardless of filter condition. Variable Air Volume optional — constant duct pressure control, useful where downstream zone dampers vary the building's actual demand (multi-room offices, schools with varied occupancy patterns).

Free cooling + cool recovery

Built-in energy-saving features: when outdoor air is cooler than indoor on a summer evening, free cooling pulls outdoor air directly through bypass dampers. Cool recovery transfers coolness from extract to supply on hot days when outdoor air is warmer than the conditioned space.

Pressure-based filter monitoring

Filter status detected by pressure transmitters with airflow-adjusted setpoint — not a simple time-based timer. Means the controller flags filter change exactly when needed, not on an arbitrary schedule. Useful for variable-occupancy buildings where filter loading rate varies.

Sensor inputs (CO₂ / humidity / temp)

Multiple analog and digital inputs for external sensors. CO₂-driven control standard for occupancy zones; humidity for changing-rooms or kitchens; temperature for night setback, free cooling activation, and frost protection on hot water coil systems.

External electrical cabinet

Topvex SC has a separate electrical cabinet with all cable connections collected at one place — facilitates commissioning and service without opening the AHU itself. RJ-45 quick connector for the NaviPad and external HMI.

Installation

Topvex SC35-R-B is commercial AHU territory — significantly bigger scope than residential MVHR. Typically 5–10 days on site for a single SC unit deployment, plus 2–4 weeks design lead-time. Best specified at first-fix stage of a new fit-out, refurbishment, or commercial newbuild.

01 Design 2–4 weeks before site Zone-by-zone airflow calculation per Building Regulations Part F (or BB101 for schools, HTM 03-01 for healthcare). SC size selected per project airflow requirement. Reheater type chosen (EL/HW/none). L or R hand confirmed. Duct schedule drawn. Condensate drain routing planned. BMS integration points specified. Acoustic silencer positions specified.
02 First-fix ductwork 3–5 days on site Galvanised or DW/144-grade ductwork installed before plasterboard, suspended ceilings or finishes. Insulated where appropriate. Acoustic silencers fitted on supply and extract — required for office and educational scopes per BB93 / BS 8233. External vents to roof or facade.
03 Plant install 1–2 days on site Topvex SC35-R-B lifted into position — typically floor-mounted in a plant room. 408 kg unit weight; lifting plan and access route confirmed in advance. Four duct unions made at the side connections. Condensate drain routed to existing waste pipework. Single-phase 230V mains supply with 20A fuse. NaviPad routed to a wall position via 3 m cable.
04 Commission 1–2 days Run NaviPad commissioning wizard. Set airflow per zone (l/s or m³/h), CAV or VAV mode, schedules, sensor inputs. Measure and verify with calibrated anemometer at every supply and extract terminal per BESA DW/143. Configure BMS handshake (Modbus / BACnet) and verify point register. Hand over O&M manual, login credentials, filter change schedule.

Configuration & sizing

SC35-R-B is a 3,150 m³/h side-connected counter-flow AHU configuration. The Topvex SC family extends from smaller sizes (~700 m³/h) up to SC100 (~7,400 m³/h) — sizing adjusted to project airflow at quote stage.

SC35-R-B configuration

3,150 m³/h supply + extract @ 115 Pa. R-hand variant, B casing. Single-phase 230V, 20A, 1.64 kW. F7 supply + M5 extract integrated. 87.9% heat recovery (EN 308 wet). 408 kg. Article 460103. £15,000 ex VAT equipment package.

Adjust airflow up — SC50 to SC100

For larger commercial scopes — large schools, healthcare facilities, supermarkets, large offices. Topvex SC50 (~5,000 m³/h) and above up to SC100 (~7,400 m³/h). Quote-on-request — sized to project brief, lead times 6–8 weeks.

Adjust airflow down — SC02 to SC25

For smaller commercial scopes — small clinics, dental practices, GP surgeries, small daycare facilities. Topvex SC02 through SC25 (~700 to 2,500 m³/h). Quote-on-request — sized to project airflow.

L or R hand variant

R (Right) on this configuration — refers to which side the supply air emerges from when viewed from the access side. L variant available for opposite-hand layouts. Selected from building services drawings; affects duct connection geometry, not performance.

Heater options

No integrated reheater on the SC35-R-B base configuration (the "N" in the SKU code). Optional add-ons: EL (electric reheater), HW (hot water coil) — for buildings with heat pump or boiler hot water available. Or add downstream coil from a separate supply.

CAV or VAV airflow control

CAV (Constant Air Volume) cascaded extract control on this SC35-R-B configuration. VAV (Variable Air Volume with constant duct pressure) optional — better for buildings with zone dampers and varied occupancy patterns. Selected at order, not field-changeable.

Condensate drain required

Counter-flow plate exchangers produce condensate when warm humid extract air meets the cooler plate — drain pan with R½ connection integrated. Plant location must accommodate routing to existing waste pipework. This is the trade-off vs rotary AHUs which transfer moisture and need no drain.

Acoustic silencers

Required for occupied office, school, retail, healthcare and fitness scopes per BB93 / BS 8233 acoustic standards. Silencers fitted on supply and extract sides reduce duct-borne noise to occupied-space targets. Specified per project — not included in base equipment.

Aftercare

Commercial AHUs serve buildings that depend on them — service downtime is operationally costly. Topvex SC35-R-B is engineered for predictable, scheduled servicing with large inspection access, removable plate exchanger, and pressure-based filter monitoring that flags change exactly when needed.

2-year manufacturer warranty

Systemair provides a 2-year manufacturer warranty on the unit as standard. Built to Eurovent certification, EN 1886 casing performance, and full ErP compliance. Mature platform — Topvex SC has been Systemair's side-connected commercial AHU range for over a decade.

Pressure-based filter monitoring

F7 + M5 filters changed when pressure transmitters indicate (not on a fixed timer). Typically every 6–12 months depending on outdoor air quality and occupancy density. Filter sets sized to unit; replacement filter pricing scales with unit size — confirmed at quote.

Removable plate exchanger

The counter-flow plate exchanger lifts out for cleaning when needed (typically every 3–5 years or sooner if airflow performance drops). Wash with mild detergent and rinse — no ammonia products. Plate weight on SC35 is a two-person lift. Far simpler servicing than rotary alternatives — no drive belts, no rotation seals, no rotor motor.

Condensate drain maintenance

Annual visual inspection of the condensate drain pan and R½ outlet to ensure free-flowing water removal. Drain pan should be clear of debris and standing water. Trap should be filled to prevent foul air ingress. CleverBloom service plan includes drain inspection as standard.

Large inspection access

Full service access from the front — main components (plate exchanger, fans, filters, heater) all reachable without dismantling adjacent ductwork. Doors open with a 16 mm key (supplied with unit).

CleverBloom commercial service plan

For office, school, retail, healthcare and HMO clients, CleverBloom offers scheduled service contracts: filter changes, plate exchanger inspection, condensate drain check, flow rate verification with calibrated anemometer, sensor recalibration, and BMS handshake testing. Quoted per project based on building size and access.

Pricing

Transparent pricing.
Grant included.

Heat pump unit only. Radiators, UFH, and emitters are on the heating page.

No items found.
fully installed
supply only

£15,000

Equipment only · 3,150 m³/h supply + extract · Eurovent certified · ex VAT


What's included

Includes Topvex SC35-R-B unit, counter-flow plate exchanger, EC plug fans, F7 supply + M5 extract filters integrated in SKU, NaviPad PD70-C control panel, two TUNE-AHU air dampers (500×400), 1-day Systemair controls setup, carriage to site £15,000

Sizing alternatives (project-specific)

SC02–SC10 (~700–1,200 m³/h, small clinics) POA
SC15–SC25 (~1,500–2,500 m³/h, medium scopes) POA
SC50–SC75 (~5,000–7,000 m³/h, larger schools/healthcare) POA
SC100 (~7,400 m³/h, large commercial) POA
Equipment total ex VAT £15,000

POA

Fully installed · equipment + design, install & commissioning


What's included

Includes Topvex SC35-R-B unit, counter-flow plate exchanger, EC plug fans, F7 supply + M5 extract filters integrated in SKU, NaviPad PD70-C control panel, two TUNE-AHU air dampers (500×400), 1-day Systemair controls setup, carriage to site £15,000
Design, install & commissioning POA

Sizing alternatives (project-specific)

SC02–SC10 (~700–1,200 m³/h, small clinics) POA
SC15–SC25 (~1,500–2,500 m³/h, medium scopes) POA
SC50–SC75 (~5,000–7,000 m³/h, larger schools/healthcare) POA
SC100 (~7,400 m³/h, large commercial) POA
Project total POA

£15,000

Equipment only · 3,150 m³/h supply + extract · Eurovent certified · ex VAT


What's included

Includes Topvex SC35-R-B unit, counter-flow plate exchanger, EC plug fans, F7 supply + M5 extract filters integrated in SKU, NaviPad PD70-C control panel, two TUNE-AHU air dampers (500×400), 1-day Systemair controls setup, carriage to site £15,000

Sizing alternatives (project-specific)

SC02–SC10 (~700–1,200 m³/h, small clinics) POA
SC15–SC25 (~1,500–2,500 m³/h, medium scopes) POA
SC50–SC75 (~5,000–7,000 m³/h, larger schools/healthcare) POA
SC100 (~7,400 m³/h, large commercial) POA
Equipment total ex VAT £15,000
Equipment
£11,200
Installation & commissioning
£4,300
Fully installed
£15,500
After £7,500 BUS grant 0% VAT until March 2027
£8,000
get a quote
Whats App instead
No items found.

Technical specifications

Airflow 3,150 m³/h 3,150 m³/h supply + 3,150 m³/h extract at 115 Pa external pressure. Face velocity 1.7 m/s. CAV (Constant Air Volume) cascaded extract control.
Heat Recovery 87.9% 87.9% temperature efficiency wet (EN 308). 81.3% dry. 83.0% Ecodesign temperature ratio. Counter-flow plate exchanger (recuperative). Stepless capacity via modulating bypass control.
Sound Level 59 dB Sound power Lwa 59 dB. Sound pressure 45 dB(A) at 3 m. Tested per EN 13053. Acoustic silencers required for occupied office, school, retail, healthcare and fitness scopes.
Filters F7 / M5 F7 supply (ISO ePM1 60%) + M5 extract (ISO ePM10 60%) — integrated into SKU code (S-SC35-R-N-ePM1/60-CE-B-C1-ePM10/60-AC). Pressure-monitored — controller alerts when change is due. Removable from inspection access.
Power Supply 230V 1ph 1×230V + N + PE, 50/60 Hz, 20 A fuse. 1.64 kW total power consumption — single-phase. SFP int 1.04 kW/(m³/s). Direct drive EC fans, supply fan efficiency 66.0%, extract fan efficiency 62.8%.
Casing C5 / EN 1886 50 mm panels, double-skinned construction. EN 1886:2007 classifications: L2 (air leakage), D2 (mechanical), T2 (thermal), TB2 (thermal bridging). C5 corrosion class (EN ISO 12944-2). Width 867 mm.
Weight & Size 408 kg 408 kg unit weight. Duct connection 500 × 400 mm (4 connections — outdoor, supply, extract, exhaust). R½ condensate drain connection. Width 867 mm. Side-connected design — best suited to floor-mounted plant room installation.
Control NaviPad Access control system with NaviPad 7" IPS touchscreen (IP54). CU27-C2 WiFi unit with 27 physical I/Os. Modbus RS485, Modbus TCP/IP, BACnet/IP. Access Connect mobile app (iOS/Android). Systemair Connect cloud service available.
Ecodesign Approved Fulfils Ecodesign 2018. NRVU/BVU. Temperature ratio 83.0% nominal. SFP int 1.04 kW/(m³/s). Internal leakage 1%. External leakage 2%. Eurovent certified. ErP compliant.

Works with

No items found.

Installed by CleverBloom

No items found.

About products

arrow

Heading 1

Heading 2

Heading 3

Heading 4

Heading 5
Heading 6

Lorem ipsum dolor sit amet, consectetur adipiscing elit, sed do eiusmod tempor incididunt ut labore et dolore magna aliqua. Ut enim ad minim veniam, quis nostrud exercitation ullamco laboris nisi ut aliquip ex ea commodo consequat. Duis aute irure dolor in reprehenderit in voluptate velit esse cillum dolore eu fugiat nulla pariatur.

Block quote

Ordered list

  1. Item 1
  2. Item 2
  3. Item 3

Unordered list

  • Item A
  • Item B
  • Item C

Text link

Bold text

Emphasis

Superscript

Subscript

line

Request a Service

Call us at 07526 985258

or leave your contact information below,
and we'll get back to you soon.

Thank you! Your message has been sent. We’ll get back to you soon!
Oops! Something went wrong. Please try again or check your details and submit again.

Ready for a better building?

Join our certified installer network — leads, products, and technical support provided.

Whats App instead
Clever Bloom - Smart Home and MVHR Ventilation Installation UK

We provide smart technology for homes and commercial spaces, ensuring transparent processes and optimal resource management.

Working hours: Mon - Sun. 8am - 8pm

Proudly serving the entire UK!

Give us a call
07526 985258
Send us an email
info@cleverbloom.co.uk
Technology catalog
AirHeatingCoolingHumidityWaterEnergyInsulation
Company
ProjectsBecome an installer
Social media
InstagramFacebooklinkedin
Documents
Privacy policyTerms and conditions
Location
Address: 3 Vickers house,  3 Hornchurch road UB10 0YG, London

© 2026 Clever Bloom — All rights reserved

Company registered in England and Wales / Company number: 14242566.